3C33 10KS-800KS
-
Digital control Online double conversion
-
Built-in output isolation transformer
-
Industrial-grade design for harsh conditions
-
Front maintenance design
-
Adaptation to various load conditions
-
Up to 4 units can be operated in parallel
- Abundant communication interfaces
- Overview
- Related Products
APPLICATIONS FIELDS
Widely used in network management centers and computers, banks, securities, taxation, communications, postal services, radio and television, public security, transportation, electric power, medical, industrial control, national defense and other important data fields.
Product Parameters:
Model | 3C33 10KS | |
Phase | Three-input three-output | |
Capacity | 10KVA 8KW | |
Input | ||
Input Voltage | 3×380VAC/400VAC/415VAC (3-phase + N or 3-phase + N line + PE (Earth) line) | |
Voltage range | 304VAC~456VAC | |
Input frequency | 50Hz±10% | |
Output | ||
Output voltage | 3 x 380VAC/400VAC /415VAC(3 phase + N) | |
AC voltage regulation | 1% | |
Factor | 0.8 | |
Output waveform | pure sine wave | |
Conversion time | 0ms | |
Output Frequency |
Mains mode : (50/60)±0.01HZ | |
Battery mode: (50/60)±0.01HZ | ||
Waveform balance | <2% (linear load); < 5% (non-linear load) | |
Dynamic adjustment time |
120°±1% (balanced load); 120°±2% (50% unbalanced load) |
|
Overload capacity | ≤110%@60min , ≤125%@10min , ≤150%@1min , >150@200ms | |
Load power factor range | 3:1 | |
Current Limit | Extreme overload, short circuit: voltage effective value limit; Impulse current: peak voltage limit | |
Bypass | ||
Types | Static switch | |
Voltage | 3 x 380VAC/400VAC/415VAC (3 phase + N) | |
Frequency | 50/60 Hz | |
Control mode | Microprocessor control | |
Conversion time | 0ms | |
Overload capacity | 150%~180% @1h~30s; 180%~>200%@30s~200ms | |
Switch to bypass | Immediately, overload 160% | |
Switching back to inversion | Automatic switching after alarm clearing | |
Maintenance bypass | ||
Types | Uninterrupted | |
Voltage | 3x 400V (3 phase + N) | |
Frequency | 50/60 Hz | |
|
Online mode | 90% |
Battery mode | 90% | |
Battery & Charging | ||
Battery quantity | 12VDCx32 (29-32 adjustable) | |
Rated voltage | 384 VDC (based on 32 adjustable) | |
Charging method | CC/CV | |
Charging current | Preset 10A, max=capacity/battery voltage | |
Charging voltage | 432 VDC (based on 32 adjustable) | |
Physical property | ||
Size(mm) | 653x405x820 | |
Package(mm) | 785x535x985 | |
Net weight (kg) | 120 | |
Gross weight(kg) | 132 |
Product Parameters:
Model | 3C33 20KS | |
Phase | Three-input three-output | |
Capacity | 20KVA 16KW | |
Input | ||
Input Voltage | 3×380VAC/400VAC/415VAC (3-phase + N or 3-phase + N line + PE (Earth) line) | |
Voltage range | 304VAC~456VAC | |
Input frequency | 50Hz±10% | |
Output | ||
Output voltage | 3 x 380VAC/400VAC /415VAC(3 phase + N) | |
AC voltage regulation | 1% | |
Factor | 0.8 | |
Output waveform | pure sine wave | |
Conversion time | 0ms | |
Output Frequency |
Mains mode : (50/60)±0.01HZ | |
Battery mode: (50/60)±0.01HZ | ||
Waveform balance | <2% (linear load); < 5% (non-linear load) | |
Dynamic adjustment time |
120°±1% (balanced load); 120°±2% (50% unbalanced load) |
|
Overload capacity | ≤110%@60min , ≤125%@10min , ≤150%@1min , >150@200ms | |
Load power factor range | 3:1 | |
Current Limit | Extreme overload, short circuit: voltage effective value limit; Impulse current: peak voltage limit | |
Bypass | ||
Types | Static switch | |
Voltage | 3 x 380VAC/400VAC/415VAC (3 phase + N) | |
Frequency | 50/60 Hz | |
Control mode | Microprocessor control | |
Conversion time | 0ms | |
Overload capacity | 150%~180% @1h~30s; 180%~>200%@30s~200ms | |
Switch to bypass | Immediately, overload 160% | |
Switching back to inversion | Automatic switching after alarm clearing | |
Maintenance bypass | ||
Types | Uninterrupted | |
Voltage | 3x 400V (3 phase + N) | |
Frequency | 50/60 Hz | |
|
Online mode | 90% |
Battery mode | 90% | |
Battery & Charging | ||
Battery quantity | 12VDCx32 (29-32 adjustable) | |
Rated voltage | 384 VDC (based on 32 adjustable) | |
Charging method | CC/CV | |
Charging current | Preset 10A, max=capacity/battery voltage | |
Charging voltage | 432 VDC (based on 32 adjustable) | |
Physical property | ||
Size(mm) | 653x405x820 | |
Package(mm) | 785x535x985 | |
Net weight (kg) | 136 | |
Gross weight(kg) | 148 |
Product Parameters:
Model | 3C33 30KS | |
Phase | Three-input three-output | |
Capacity | 30KVA 24KW | |
Input | ||
Input Voltage | 3×380VAC/400VAC/415VAC (3-phase + N or 3-phase + N line + PE (Earth) line) | |
Voltage range | 304VAC~456VAC | |
Input frequency | 50Hz±10% | |
Output | ||
Output voltage | 3 x 380VAC/400VAC /415VAC(3 phase + N) | |
AC voltage regulation | 1% | |
Factor | 0.8 | |
Output waveform | pure sine wave | |
Conversion time | 0ms | |
Output Frequency |
Mains mode : (50/60)±0.01HZ | |
Battery mode: (50/60)±0.01HZ | ||
Waveform balance | <2% (linear load); < 5% (non-linear load) | |
Dynamic adjustment time |
120°±1% (balanced load); 120°±2% (50% unbalanced load) |
|
Overload capacity | ≤110%@60min , ≤125%@10min , ≤150%@1min , >150@200ms | |
Load power factor range | 3:1 | |
Current Limit | Extreme overload, short circuit: voltage effective value limit; Impulse current: peak voltage limit | |
Bypass | ||
Types | Static switch | |
Voltage | 3 x 380VAC/400VAC/415VAC (3 phase + N) | |
Frequency | 50/60 Hz | |
Control mode | Microprocessor control | |
Conversion time | 0ms | |
Overload capacity | 150%~180% @1h~30s; 180%~>200%@30s~200ms | |
Switch to bypass | Immediately, overload 160% | |
Switching back to inversion | Automatic switching after alarm clearing | |
Maintenance bypass | ||
Types | Uninterrupted | |
Voltage | 3x 400V (3 phase + N) | |
Frequency | 50/60 Hz | |
|
Online mode | 91% |
Battery mode | 91% | |
Battery & Charging | ||
Battery quantity | 12VDCx32 (29-32 adjustable) | |
Rated voltage | 384 VDC (based on 32 adjustable) | |
Charging method | CC/CV | |
Charging current | Preset 10A, max=capacity/battery voltage | |
Charging voltage | 432 VDC (based on 32 adjustable) | |
Physical property | ||
Size(mm) | 820x433x1160 | |
Package(mm) | 960x560x1333 | |
Net weight (kg) | 242 | |
Gross weight(kg) | 257 |
Product Parameters:
Model | 3C33 40KS | |
Phase | Three-input three-output | |
Capacity | 40KVA 32KW | |
Input | ||
Input Voltage | 3×380VAC/400VAC/415VAC (3-phase + N or 3-phase + N line + PE (Earth) line) | |
Voltage range | 304VAC~456VAC | |
Input frequency | 50Hz±10% | |
Output | ||
Output voltage | 3 x 380VAC/400VAC /415VAC(3 phase + N) | |
AC voltage regulation | 1% | |
Factor | 0.8 | |
Output waveform | pure sine wave | |
Conversion time | 0ms | |
Output Frequency |
Mains mode : (50/60)±0.01HZ | |
Battery mode: (50/60)±0.01HZ | ||
Waveform balance | <2% (linear load); < 5% (non-linear load) | |
Dynamic adjustment time |
120°±1% (balanced load); 120°±2% (50% unbalanced load) |
|
Overload capacity | ≤110%@60min , ≤125%@10min , ≤150%@1min , >150@200ms | |
Load power factor range | 3:1 | |
Current Limit | Extreme overload, short circuit: voltage effective value limit; Impulse current: peak voltage limit | |
Bypass | ||
Types | Static switch | |
Voltage | 3 x 380VAC/400VAC/415VAC (3 phase + N) | |
Frequency | 50/60 Hz | |
Control mode | Microprocessor control | |
Conversion time | 0ms | |
Overload capacity | 150%~180% @1h~30s; 180%~>200%@30s~200ms | |
Switch to bypass | Immediately, overload 160% | |
Switching back to inversion | Automatic switching after alarm clearing | |
Maintenance bypass | ||
Types | Uninterrupted | |
Voltage | 3x 400V (3 phase + N) | |
Frequency | 50/60 Hz | |
|
Online mode | 91% |
Battery mode | 91% | |
Battery & Charging | ||
Battery quantity | 12VDCx32 (29-32 adjustable) | |
Rated voltage | 384 VDC (based on 32 adjustable) | |
Charging method | CC/CV | |
Charging current | Preset 10A, maximum 40A | |
Charging voltage | 432 VDC (based on 32 adjustable) | |
Physical property | ||
Size(mm) | 820x433x1160 | |
Package(mm) | 960x560x1333 | |
Net weight (kg) | 419 | |
Gross weight(kg) | 445 |
Product Parameters:
Model | 3C33 60KS | |
Phase | Three-input three-output | |
Capacity | 60KVA 48KW | |
Input | ||
Input Voltage | 3×380VAC/400VAC/415VAC (3-phase + N or 3-phase + N line + PE (Earth) line) | |
Voltage range | 304VAC~456VAC | |
Input frequency | 50Hz±10% | |
Output | ||
Output voltage | 3 x 380VAC/400VAC /415VAC(3 phase + N) | |
AC voltage regulation | 1% | |
Factor | 0.8 | |
Output waveform | pure sine wave | |
Conversion time | 0ms | |
Output Frequency |
Mains mode : (50/60)±0.01HZ | |
Battery mode: (50/60)±0.01HZ | ||
Waveform balance | <2% (linear load); < 5% (non-linear load) | |
Dynamic adjustment time |
120°±1% (balanced load); 120°±2% (50% unbalanced load) |
|
Overload capacity | ≤110%@60min , ≤125%@10min , ≤150%@1min , >150@200ms | |
Load power factor range | 3:1 | |
Current Limit | Extreme overload, short circuit: voltage effective value limit; Impulse current: peak voltage limit | |
Bypass | ||
Types | Static switch | |
Voltage | 3 x 380VAC/400VAC/415VAC (3 phase + N) | |
Frequency | 50/60 Hz | |
Control mode | Microprocessor control | |
Conversion time | 0ms | |
Overload capacity | 150%~180% @1h~30s; 180%~>200%@30s~200ms | |
Switch to bypass | Immediately, overload 160% | |
Switching back to inversion | Automatic switching after alarm clearing | |
Maintenance bypass | ||
Types | Uninterrupted | |
Voltage | 3x 400V (3 phase + N) | |
Frequency | 50/60 Hz | |
|
Online mode | 92% |
Battery mode | 93% | |
Battery & Charging | ||
Battery quantity | 12VDCx32 (29-32 adjustable) | |
Rated voltage | 384 VDC (based on 32 adjustable) | |
Charging method | CC/CV | |
Charging current | Preset 10A, maximum 40A | |
Charging voltage | 432 VDC (based on 32 adjustable) | |
Physical property | ||
Size(mm) | 820x433x1160 | |
Package(mm) | 960x560x1333 | |
Net weight (kg) | 290 | |
Gross weight(kg) | 305 |
Product Parameters:
Model | 3C33 80KS | |
Phase | Three-input three-output | |
Capacity | 80KVA 64KW | |
Input | ||
Input Voltage | 3×380VAC/400VAC/415VAC (3-phase + N or 3-phase + N line + PE (Earth) line) | |
Voltage range | 304VAC~456VAC | |
Input frequency | 50Hz±10% | |
Output | ||
Output voltage | 3 x 380VAC/400VAC /415VAC(3 phase + N) | |
AC voltage regulation | 1% | |
Factor | 0.8 | |
Output waveform | pure sine wave | |
Conversion time | 0ms | |
Output Frequency |
Mains mode : (50/60)±0.01HZ | |
Battery mode: (50/60)±0.01HZ | ||
Waveform balance | <2% (linear load); < 5% (non-linear load) | |
Dynamic adjustment time |
120°±1% (balanced load); 120°±2% (50% unbalanced load) |
|
Overload capacity | ≤110%@60min , ≤125%@10min , ≤150%@1min , >150@200ms | |
Load power factor range | 3:1 | |
Current Limit | Extreme overload, short circuit: voltage effective value limit; Impulse current: peak voltage limit | |
Bypass | ||
Types | Static switch | |
Voltage | 3 x 380VAC/400VAC/415VAC (3 phase + N) | |
Frequency | 50/60 Hz | |
Control mode | Microprocessor control | |
Conversion time | 0ms | |
Overload capacity | 150%~180% @1h~30s; 180%~>200%@30s~200ms | |
Switch to bypass | Immediately, overload 160% | |
Switching back to inversion | Automatic switching after alarm clearing | |
Maintenance bypass | ||
Types | Uninterrupted | |
Voltage | 3x 400V (3 phase + N) | |
Frequency | 50/60 Hz | |
|
Online mode | 92% |
Battery mode | 93% | |
Battery & Charging | ||
Battery quantity | 12VDCx32 (29-32 adjustable) | |
Rated voltage | 384 VDC (based on 32 adjustable) | |
Charging method | CC/CV | |
Charging current | Preset 10A, maximum 40A | |
Charging voltage | 432 VDC (based on 32 adjustable) | |
Physical property | ||
Size(mm) | 975*635*1325 | |
Package(mm) | 1100*780*1490 | |
Net weight (kg) | 136 | |
Gross weight(kg) | 148 |
Product Parameters:
Model | 3C33 100-800KS | |
Phase | Three-input three-output | |
Capacity | 100-800KVA 80-640KW | |
Input | ||
Input Voltage | 3×380VAC/400VAC/415VAC (3-phase + N or 3-phase + N line + PE (Earth) line) | |
Voltage range | 304VAC~456VAC | |
Input frequency | 50Hz±10% | |
Output | ||
Output voltage | 3 x 380VAC/400VAC /415VAC(3 phase + N) | |
AC voltage regulation | 1% | |
Factor | 0.8 | |
Output waveform | pure sine wave | |
Conversion time | 0ms | |
Output Frequency |
Mains mode : (50/60)±0.01HZ | |
Battery mode: (50/60)±0.01HZ | ||
Waveform balance | <2% (linear load); < 5% (non-linear load) | |
Dynamic adjustment time |
120°±1% (balanced load); 120°±2% (50% unbalanced load) |
|
Overload capacity | ≤110%@60min , ≤125%@10min , ≤150%@1min , >150@200ms | |
Load power factor range | 3:1 | |
Current Limit | Extreme overload, short circuit: voltage effective value limit; Impulse current: peak voltage limit | |
Bypass | ||
Types | Static switch | |
Voltage | 3 x 380VAC/400VAC/415VAC (3 phase + N) | |
Frequency | 50/60 Hz | |
Control mode | Microprocessor control | |
Conversion time | 0ms | |
Overload capacity | 150%~180% @1h~30s; 180%~>200%@30s~200ms | |
Switch to bypass | Immediately, overload 160% | |
Switching back to inversion | Automatic switching after alarm clearing | |
Maintenance bypass | ||
Types | Uninterrupted | |
Voltage | 3x 400V (3 phase + N) | |
Frequency | 50/60 Hz | |
|
Online mode | 93% |
Battery mode | 93% | |
Battery & Charging | ||
Battery quantity | 12VDCx32 (29-32 adjustable) | |
Rated voltage | 384 VDC (based on 32 adjustable) | |
Charging method | CC/CV | |
Charging current | Preset 10A, maximum 40A | |
Charging voltage | 432 VDC (based on 32 adjustable) | |
Physical property | ||
Size(mm) | - | |
Package(mm) | - | |
Net weight (kg) | - | |
Gross weight(kg) | - |