Rack-mounted UPS 1KVA-10KVA
- Truly achieve online double conversion
-
Microprocessor control ensures high reliability .
-
Input power factor correction
-
Output power factor up to 0.8
-
Wide utility input range (110V-300V) .
-
Efficient frequency conversion mode
-
Compatible with generators
- External battery ups charging current up to 6A
- Overview
- Related Products
APPLICATIONS FIELDS
Widely used in network management centers and computers, banks, securities, taxation, communications, postal services, radio and television, public security, transportation, electric power, medical, industrial control, national defense and other important data fields.
Model |
C1KR(S) |
C2KR(S) |
C3KR(S) |
C6KR(S) |
C10KR(S) |
|||||||
Phase |
Single phase |
|||||||||||
Capacity |
1KVA/800W |
2KVA/1600W |
3KVA/2400W |
6KVA/4800W |
10KVA/8000W |
|||||||
Input |
||||||||||||
Input voltage |
100/110/115/120/127VAC OR 200/208/220/230/240VCA |
208/220/230/240VAC |
||||||||||
Voltage range |
55-145VAC/110-300VAC@50% load85-140VAC/160-280VAC@100% load |
110-300VAC±3%@50% load176-300VAC±3%@100%load |
||||||||||
Input frequency |
40Hz-70Hz |
46-54Hz OR 56-64Hz |
||||||||||
Factor |
≥0.99@100%load |
|||||||||||
Output |
||||||||||||
Output voltage |
100/110/115/120/127VAC OR 200/208/220/230/240VCA |
208/220/230/240VCA |
||||||||||
Voltage range (battery mode) |
±1% |
|||||||||||
Frequency synchronous range |
47-53Hz/57-63Hz |
46-54Hz/56-64Hz |
||||||||||
Frequency range (battery mode) |
50Hz±0.25Hz/60Hz±0.3Hz |
50Hz/60Hz±0.1Hz |
||||||||||
Peak factor |
3:01 |
|||||||||||
Waveform balance |
≤3%THD (Linear load )≤6%THD (Nonlinear load) |
≤3%THD (Linear load )≤5%THD (Nonlinear load) |
||||||||||
Conversion time |
0ms |
|||||||||||
Output waveform |
Pure sine wave |
|||||||||||
Efficiency |
||||||||||||
Mains power mode |
92% |
92% |
92% |
92% |
93% |
|||||||
Battery mode |
90% |
90% |
90% |
90% |
91% |
|||||||
Battery |
||||||||||||
Stardard UPS |
Battery model |
12V/7AH |
12V/9AH |
|||||||||
Battery quantity |
2 |
4 |
6 |
16 |
20 |
16 |
20 |
|||||
charging time |
Charge to 90% in 4 hours |
Charge to 90% in 9 hours |
||||||||||
Maximum charging current |
1.0A (Max) |
1A/2A (adjustable) |
||||||||||
Charging voltage±1% |
27.4VDC |
54.7VDC |
82.1VDC |
218.4VDC |
273VDC |
218.4VDC |
273VDC |
|||||
External battery UPS |
Battery model |
Depending on the applicant |
||||||||||
Battery quantity |
2 |
3 |
4 |
6 |
8 |
6 |
8 |
16-20 |
||||
Maximum charging current |
1.0A/2.0A/4.0A/6.0A |
1A/2A/4A/6A |
||||||||||
Charging voltage ±1% |
27.4 VDC |
41 VDC |
54.7 VDC |
82.1 VDC |
109.4 VDC |
82.1 VDC |
109.4 VDC |
218.4VDC±1%(Based on 16pcs batteries) |
||||
Display description |
||||||||||||
LCD |
Load size, battery capacity, municipal power mode, battery mode, bypass mode, fault indication |
|||||||||||
|
||||||||||||
Stardard UPS |
Size (MM) |
310*438*88 |
410*438*88 |
630*438*88 |
ups : 500*438*88 battery: 668*438*88 |
ups : 500*438*88 battery: 668*438*133 |
ups : 580*438*133 battery: 580*438*133 |
|||||
Weight (KG) |
10 |
17 |
25.6 |
ups:15 battery: 48 |
ups:15 battery: 61 |
ups:18 battery: 51 |
ups:18 battery:61 |
|||||
External battery UPS |
Size (MM) |
310*438*88 |
410*438*88 |
500*438*88 |
580*438*133 |
|||||||
Weight (KG) |
5.6 |
8.6 |
13 |
17 |
||||||||
Working environment |
||||||||||||
Humidity |
20-90%RH@0-40℃(No condensation) |
|||||||||||
Noise |
<50dBA@1m |
|||||||||||
Control management |
||||||||||||
Intelligent RS-232/USB |
Be in favor of Support Windows®2000/2003/XP/Vista/2008, Windows®7/8, Linux, MAC |
|||||||||||
Optional SNMP |
Power management support SNMP and network management |